Installation
Illustration 3.15 Basic Wiring Schematic Drawing
NOTICE
There is no access to UDC- and UDC+ on the following units:
IP20, 380–480 V, 30–90 kW (40–125 hp)
IP20, 200–240 V, 15–45 kW (20–60 hp)
IP20, 525–600 V, 1.5–90 kW (2.0–125 hp)
IP54, 380–480 V, 22–90 kW (30–125 hp)

3.2.6 Acoustic Noise or Vibration

If the motor or the equipment driven by the motor - for
example, a fan - is making noise or vibrations at certain
frequencies, configure the following parameters or
parameter groups to reduce or eliminate the noise or
vibrations:
Parameter group 4-6* Speed Bypass.
Set parameter 14-03 Overmodulation to [0] Off.
BAS-SVX58D-EN
TR150 and TR170 Quick Guide
08/2020 All rights reserved.
Switching pattern and switching frequency
parameter group 14-0* Inverter Switching.
Parameter 1-64 Resonance Damping.