Trane TR150 Quick Manual page 38

Hide thumbs Also See for TR150:
Table of Contents

Advertisement

Warnings and Alarms
Fault
Alarm/
Fault text
number
warning bit
number
57
AMA timeout
58
AMA internal
59
25
Current limit
60
44
External Interlock
Heat sink
66
26
Temperature Low
69
1
Pwr. Card Temp
Illegal FC configu-
70
36
ration
Illegal power
79
section configu-
ration
80
29
Drive initialised
87
47
Auto DC Braking
95
40
Broken Belt
126
Motor Rotating
200
Fire Mode
Fire Mode Limits
202
Exceeded
250
New sparepart
251
New Typecode
Table 5.1 Warnings and Alarms
BAS-SVX58D-EN
TR150 and TR170 Quick Guide
Warning
Alarm
Trip
Cause of problem
locked
Try to start the AMA again a number of times, until the AMA
is carried out.
NOTICE
X
Repeated runs may heat the motor to a level where
the resistance R
however, this is not critical.
X
X
Contact the local Trane supplier.
The current is higher than the value in parameter 4-18 Current
X
Limit.
External interlock has been activated. To resume normal
operation, apply 24 V DC to the terminal programmed for
X
external interlock and reset the frequency converter (via
serial communication, digital I/O, or by pressing the [Reset]
key on the LCP).
This warning is based on the temperature sensor in the IGBT
X
module (on 400 V, 30–90 kW (40–125 hp) and 600 V units).
The temperature sensor on the power card exceeds the
X
X
X
upper or lower limits.
X
X
The control card and power card are not matched.
X
X
Internal fault. Contact the local Trane supplier.
X
All parameter settings are initialized to default settings.
X
The frequency converter is auto DC braking.
Torque is below the torque level set for no load, indicating a
X
X
broken belt. See parameter group 22-6* Broken Belt Detection.
X
High back EMF voltage. Stop the rotor of the PM motor.
X
Fire mode has been activated.
X
Fire mode has suppressed 1 or more warranty voiding alarms.
The power or switch mode power supply has been
X
X
exchanged (on 400 V, 30–90 kW (40–125 hp) and 600 V
units). Contact the local Trane supplier.
The frequency converter has a new type code (on 400 V, 30–
X
X
90 kW (40–125 hp) and 600 V units). Contact the local Trane
supplier.