Ambient Conditions - Trane TR150 Quick Manual

Hide thumbs Also See for TR150:
Table of Contents

Advertisement

Specifications
3) UL applications 300 V AC 2 A.
Control Card, 10 V DC Output
Terminal number
Output voltage
Maximum load

6.4.10 Ambient Conditions

Enclosure protection rating
Enclosure kit available
Vibration test
Maximum relative humidity
Aggressive environment (IEC 60721-3-3), coated (standard) enclosure sizes H1–H5
Aggressive environment (IEC 60721-3-3), non-coated enclosure sizes H6–H10
Aggressive environment (IEC 60721-3-3), coated (optional) enclosure sizes H6–H10
Aggressive environment (IEC 60721-3-3), non-coated enclosure sizes I2–I8
Test method according to IEC 60068-2-43 H2S (10 days)
1)
Ambient temperature
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance, enclosure sizes H1–H5 and I2–I4
Minimum ambient temperature at reduced performance, enclosure sizes H6–H10 and I6–I8
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
Derating for high altitude, see chapter 6.3.2 Derating for Low Air Pressure and High Altitudes.
Safety standards
EMC standards, Emission
EMC standards, Immunity
2)
Energy efficiency class
1) Refer to Special Conditions in the design guide for:
Derating for high ambient temperature.
Derating for high altitude.
2) Determined according to EN 50598-2 at:
Rated load.
90% rated frequency.
Switching frequency factory setting.
Switching pattern factory setting.
BAS-SVX58D-EN
TR150 and TR170 Quick Guide
5–95% (IEC 60721-3-3; Class 3K3 (non-condensing)) during operation
See maximum output current at 40/50/70 °C (104/122/158 °F) in chapter 6.1.2 3x380–480 V AC.
EN 61800-3, EN 61000-3-12, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
08/2020 All rights reserved.
IP20, IP54 (Not for outdoor installation)
-30 to +65/70 °C (-22 to +149/158°F)
EN/IEC 61800-5-1, UL 508C
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61000-4-5, EN 61000-4-6
50
10.5 V ±0.5 V
25 mA
IP21, TYPE 1
1.0 g
Class 3C3
Class 3C2
6
6
Class 3C3
Class 3C2
0 °C (32 °F)
-20 °C (-4 °F)
-10 °C (14 °F)
1000 m (3281 ft)
3000 m (9843 ft)
IE2