3. Setting
3.4 Setting Menu 3: Display Settings (Setting Maximum Scale, Active Energy Measurement, and
Harmonic Display, etc.)
⑤Power factor scale
DISPLAY
SET
⑥Expanded counting
DISPLAY
SET
⑦Harmonics
SET
Setting menu
●Accuracy is defined to rated current. Although the maximum scale may display 120% or more of
rated current and rated voltage in order to make a scale easy to read depending on the settings of
VT/direct voltage and CT primary current, current input is within 100% of rated current.
●Even if a display pattern is selected that cannot display active power, reactive power, active energy,
Note
and reactive energy, it is possible to display the sign according to 2 quadrant / 4 quadrant
measurement of the power factor and reactive power due to ⑥Expanded counting , so setting
items for ⑥Expanded counting will be displayed.
Set the power factor scale.
If you have not set power factor to "Display pattern",
this display will be skipped.
-0.5 to 1 to 0.5
Set the combinations of imported / exported and lag / lead for active energy and
reactive energy you want to display, and set the measurement method for reactive
energy.
Combination
Wh
(Setting value)
Imported
Exported
Note: For more information about the measurement method for reactive energy,
refer to page 54.
Combination I, II ⇒It is suitable for the counting of equipment without the private
electric generator and the reactive power of the capacitor load at
the power factor = 0, generally.
Combination III, IV⇒It is suitable for the counting of equipment with the private electric
generator.
<Example
Screen>
Combination I
:Imported
:Exported
Depending on the above combination and the measurement element which
set in ②Display pattern of the setting menu 1, the energies displayed at the
additional screen are as below.
Wh
Wh
-Wh
varh
varh
VAh
VAh
Note: Wh:Wh(imported), -Wh:Wh(exported), varh:varh(imported LAG)
Set
"on or off" of
the harmonic measurement display.
oFF
on
(Not displayed)
(Displayed)
When the display is set to "on," the harmonic measured value can be displayed on
an additional screen of the display pattern.
According to the setting flow diagram (page 14), save the changed
contents, or continue to the other setting menu.
-0 to 1 to 0
Display
varh
Imported
Exported
lag
lead
lag
Combination III
Combination II
varh
lead
Additional Screen
-Wh
varh(imported LEAD)
varh(exported LAG) varh(exported LEAD)
- 22 -
Reactive energy
measurement
method
lead
2 quadrant
measurement
4 quadrant
measurement
Combination IV
varh
lag