Installation
Fig. 31:
Busbar for busbar current up to 1250 A
Fig. 32:
Busbars for busbar current of 1600, 2000 and 2500 A
Busbar lengths
90/266
Busbars (overview)
With the help of the following tables, the required busbar lengths between two adjacent
panels each can be determined by means of the panel width and the arrangement of the
bushings at the switching-device vessel.
If a dummy panel is installed between the switchgear panels, a busbar that is longer by the
width of a dummy panel must be installed (+300 mm or +600 mm).
The busbar lengths for the provided panels can be found in the order documentation.
Revision 02 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 806-9004.9
K1 Reference dimension for
K2 Reference dimension for
INFORMATION
Cap
Contact half-shell
Busbar
Adjustment component
End adapter
Busbar insulation
Earthing cable
Bushing
Earthing terminal
Cross adapter
Threaded stud M12/M16
Conical spring washer,
DIN 6796-12
Hexagon nut, ISO 4032-M 12
Screw-type cone
Coupling end adapter
Copper washer, galvanized
Lock washer
Connection stud
Coupling cross adapter
Adapter lip
busbar length
threaded stud