Push the interrogation lever downwards
again and hold it.
10
➭
Remove the operating lever.
✔
The interrogation lever and the control gate
move to their initial position.
13
➭
Insert the operating lever.
Turn it counterclockwise 180°.
✔
The left-hand disconnector is in the OPEN
position.
240/266
8
➭
Push the left-hand control gate to the right
and hold it.
✔
The actuating opening of the left-hand
earthing switch is open.
11
➭
Close the circuit-breaker.
✔
The circuit-breaker is in the CLOSED
position. The feeder is earthed through the
left-hand disconnector.
14
➭
Remove the operating lever.
✔
The control gate moves to its initial position.
Revision 02 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 806-9004.9
9
➭
Insert the operating lever.
Turn it clockwise 180°.
✔
The left-hand disconnector is in the READY-
TO-EARTH position.
12
➭
Push the right-hand control gate to the right
and hold it.
✔
The actuating opening of the right-hand
earthing switch is open.
15
➭
To de-earth the feeder,
open the circuit-breaker.
✔
The circuit-breaker is in the OPEN position.
The earthing of the feeder has been