806-9004.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 02
Designation
Front plate
Side plate
Side plate
Mounting the side plates
Before the horizontal pressure relief duct can be installed, the switchgear termination must be
mounted (see page 121, "Installing the switchgear termination").
Perform the installation from the front, starting with the left end panel.
Installation with lateral evacuation to the left is shown here as an example.
If a higher low-voltage compartment is mounted, it is not possible to install the horizontal
pressure relief duct from the front.
➭ Install from the top or from the side.
Or
➭ Remove the low-voltage compartment and install from the front.
➭ Place the left-hand side plate ① onto the switchgear termination ③ .
Detailed designation
Front plate, closed
Side plate, closed, left side
Side plate, closed, right side
INFORMATION
Illustration
Side plate
Pre-assembled
evacuation
Switchgear termination
Installation
115/266