16
➭
Push the interrogation lever downwards
again and hold it.
19
➭
Remove the operating lever.
✔
The interrogation lever and the control gate
move to their initial position.
806-9004.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 02
17
➭
Push the left-hand control gate to the right
and hold it.
✔
The actuating opening of the left-hand
earthing switch is open.
18
➭
Insert the operating lever.
Turn it counterclockwise 180°.
✔
The left-hand disconnector is in the OPEN
position.
Operation
241/266