806-9004.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 02
• IEEE 693-2005 "Recommended Practice for Seismic Design of Substations".
For installation on even and rigid concrete or steel structure (without considering building
influences), the tested ground accelerations meet the following requirements:
• Uniform Building Code 1997 (UBC) – Zone 4
• California Building Code 1998 (CBC) – Zone 4
• IEEE 693-2005 – High required response spectrum.
7
Panel versions
Panel type
LS
Circuit-breaker panel
TR
Switch-disconnector panel with HV HRC fuses
ME
Metering panel
VS
Vacuum contactor panel with HV HRC fuses
RK
Ring-main panel
LK
Bus sectionalizer panel (single bay)
Bus sectionalizer panel (double bay)
TS
Disconnector panel
aME
Air-insulated metering panel
EB
Auxiliary transformer panel with switch-fuse combination
8
Examples for panel versions
Fig. 3:
Circuit-breaker panel
①
Voltage transformer at the busbar (option)
②
Current transformer at the busbar (option)
③
Pressure relief duct
④
Busbar
⑤
Switching-device vessel with circuit-breaker and
three-position disconnector
⑥
Current transformer at the cable connection
(option)
⑦
Voltage transformer (option)
⑧
Feeder cables with cable plugs
⑨
Current transformer (option)
⑩
Cable compartment cover
⑪
Front cover with control board
⑫
Bay controller (option)
⑬
Low-voltage compartment
Description
Panel width
[mm]
450/600
600
600
600
450
1 x 600
1x 900
2 x 600
600
900
900
11/266