Siemens NXPLUS C Installation And Operating Instructions Manual page 54

Fixed-mounted circuit-breaker switchgear up to 38 kv, extendable single busbar, metal-enclosed, gas-insulated
Table of Contents

Advertisement

Description
54/266
Transformer
Operating
Rated
Relative
voltage
power
impedance
voltage
U
S
u
N
r
K
[kV]
[kVA]
%
10.0...12.0
315
4
400
4
500
4
630
4
800
5...6
1000
5...6
1250
5..6
12.4...13.4
20
4
30
4
50
4
Revision 02 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 806-9004.9
HV HRC fuse-link
Rated
Rated
Min. operating/
current
current
rated voltage
I
I
U
r
r
r
[A]
[A]
[kV]
18.3
31.5
6...12
10...17.5
10...24
40
6...12
10...17.5
10...24
23.1
40
6...12
10...17.5
10...24
50
6...12
10...17.5
10...24
29
50
6...12
10...17.5
10...24
63
6...12
10...24
36.4
63
6...12
10...17.5
6...12
10...24
80
6...12
10...24
46.2
63
6...12
80
58
100
6..12
10...24
72
125
6..12
0.94
4
10...24
1.4
6.3
10...24
2.4
10
10...17.5
10...24
Reference
Order No. SIBA
dimension
e
[mm]
292
30 004 13.31,5
442
30 101 13.31,5
292
30 221 13.31,5
442
30 231 13.31,5
30 006 13.31,5
292
30 004 13.40
442
30 101 13.40
292
30 221 13.40
442
30 231 13.40
30 006 13.40
292
30 004 13.40
442
30 101 13.40
292
30 221 13.40
442
30 231 13.40
30 006 13.40
292
30 004 13.50
442
30 101 13.50
292
30 221 13.50
442
30 232 13.50
30 014 13.50
292
30 004 13.50
442
30 101 13.50
292
30 221 13.50
442
30 232 13.50
30 014 13.50
292
30 012 43.63
442
30 014 43.63
292
30 012 13.63
442
30 102 13.63
30 232 13.63
292
30 012 43.63
442
30 014 43.63
292
30 012 43.80
442
30 102 43.80
30 014 43.80
292
30 012 13.63
442
30 102 13.63
292
30 012 43.80
442
30 102 43.80
292
30 012 43.100
442
30 102 43.100
30 022 43.100
292
30 020 43.125
442
30 103 43.125
442
30 006 13.4
442
30 006 13.6,3
30 231 13.6,3
442
30 231 13.10
30 006 13.10

Hide quick links: