Installing A Voltage Transformer On The Busbar - Siemens NXPLUS C Installation And Operating Instructions Manual

Fixed-mounted circuit-breaker switchgear up to 38 kv, extendable single busbar, metal-enclosed, gas-insulated
Table of Contents

Advertisement

Installation
Fig. 42:
Voltage transformer installed on the busbar
Fig. 43:
Detail view from the front: Connection of the busbar to the voltage
transformer
102/266
Fig. 41:
Wire routing (air-insulated metering panel)
15.7

Installing a voltage transformer on the busbar

The voltage transformers are delivered separately. For installation, the busbars must be
installed and accessible from the front. If required, remove any installed low-voltage
compartments. If a damping resistor is present, the damping resistor must be removed from
the low-voltage compartment.
Revision 02 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 806-9004.9
Vertical wiring duct (only for
connecting wires with steel tube)
Low-voltage compartment
Right-hand wiring duct
Voltage transformer
Storage box
Voltage transformer frame
M6 bolt with contact washer
Plain washer (DIN EN ISO 7093-1-8)
M8x20 bolt-and-washer assembly
Cast-resin bushing of the voltage transformer
Centering nut (tightening torque: 10 Nm)
M12* hexagon nut
(tightening torque: 50 Nm)
Conical spring washer*
Contact half-shell*
M12/M16 threaded stud
(tightening torque: 10 Nm)*
End adapter or cross adapter
Cover frame
*
Component pre-installed on end adapter or
cross adapter

Hide quick links: