Installation
Fig. 42:
Voltage transformer installed on the busbar
Fig. 43:
Detail view from the front: Connection of the busbar to the voltage
transformer
102/266
Fig. 41:
Wire routing (air-insulated metering panel)
15.7
Installing a voltage transformer on the busbar
The voltage transformers are delivered separately. For installation, the busbars must be
installed and accessible from the front. If required, remove any installed low-voltage
compartments. If a damping resistor is present, the damping resistor must be removed from
the low-voltage compartment.
Revision 02 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 806-9004.9
①
Vertical wiring duct (only for
connecting wires with steel tube)
②
Low-voltage compartment
③
Right-hand wiring duct
①
Voltage transformer
②
Storage box
③
Voltage transformer frame
④
M6 bolt with contact washer
⑤
Plain washer (DIN EN ISO 7093-1-8)
⑥
M8x20 bolt-and-washer assembly
Cast-resin bushing of the voltage transformer
⑦
⑧
Centering nut (tightening torque: 10 Nm)
⑨
M12* hexagon nut
(tightening torque: 50 Nm)
⑩
Conical spring washer*
⑪
Contact half-shell*
⑫
M12/M16 threaded stud
(tightening torque: 10 Nm)*
⑬
End adapter or cross adapter
⑭
Cover frame
*
Component pre-installed on end adapter or
cross adapter