Switching after
emergency operation
806-9004.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 02
➭ EARTHING function: Turn the operating lever with emergency adapter counterclockwise
until the outer slots on the emergency adapter are both vertical.
✔ The switch position indicator is in the OPEN position.
➭ Remove the operating lever.
➭ Pull the emergency adapter off of the operating lever. Place the emergency adapter in the
service flap.
✔ The three-position switch can be operated electrically again.
Perform additional switching operations by hand without the emergency adapter.