Closing the service flap
806-9004.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 02
Risk of injury when closing the service flap
Fingers can be trapped between service flap and switchgear front.
➭ Hold the service flap firmly by the provided handle when closing it and close it in a
controlled manner.
Service flap slamming closed
Can damage the switchgear.
➭ Hold the service flap firmly by the provided handle and close it in a controlled manner.
➭ Carefully close the service flap ① by the handle ③ .
➭ Fold in the handle ③ .
➭ If applicable, close the lock ② on the service flap.
22.9

Operating tools

Operating lever
Use of incorrect operating levers
Using incorrect operating levers can damage or deactivate the safety equipment of the
switchgear.
➭ Use only the original Siemens operating levers corresponding to the switchgear type.
Operating lever for slow motion mechanism
Fig. 138: Operating lever for
DISCONNECTING function
(black handles)
Switching operation
DISCONNECTING
EARTHING/READY-TO-EARTH
Operating levers for spring-operated mechanism and spring-operated/stored-energy
mechanism
Fig. 140: Operating lever for charging the
operating spring (black handles)
Switching operation
Charging the operating spring
EARTHING
CAUTION
NOTICE
NOTICE
Fig. 139: Operating lever for EARTHING
or READY-TO-EARTH function
(red handles)
Color of the handles
Operation
Black
Turn the operating lever 180°.
red
Fig. 141: Operating lever for EARTHING
function (red handles)
Color of the handles
Operation
Black
Turn the operating lever straight as far as it
will go.
red
Operation
193/266