Siemens NXPLUS C Installation And Operating Instructions Manual page 234

Fixed-mounted circuit-breaker switchgear up to 38 kv, extendable single busbar, metal-enclosed, gas-insulated
Table of Contents

Advertisement

Operation
4
Remove the operating lever.
The interrogation lever and the control gate
move to their initial position.
7
Insert the operating lever.
Turn it clockwise 180°.
The left-hand disconnector is in the READY-
TO-EARTH position.
10
Push the locking device upwards. Fit a
padlock.
234/266
5
Push the interrogation lever downwards
again and hold it.
8
Remove the operating lever.
The interrogation lever and the control gate
move to their initial position.
Revision 02 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 806-9004.9
6
Push the left-hand control gate to the right
and hold it.
The actuating opening of the left-hand
earthing switch is open.
9
To earth the right-hand busbar system,
close the circuit-breaker.
The circuit-breaker is in the CLOSED
position. The right-hand busbar system is
earthed.