Breaker Data Adapter; Application; View; Indicators - Siemens UL 1066 Operating Instructions Manual

Low voltage power circuit breaker
Table of Contents

Advertisement

9.4

Breaker Data Adapter

9.4.1

Application

The Breaker Data Adapter (BDA) makes it possible to parameterize, operate and monitor the circuit breaker without additional software by
means of a browser-capable input/output device (e.g. a laptop). This is possible for circuit breakers equipped with trip units of the types
ETU745 - 776. On trip units ETU745 and ETU748, however, the basic protective functions cannot be parameterized. These are adjusted
solely by using the rotary coding switches.
Communication with the electronic system of the circuit breaker takes place via the c. For this purpose, the BDA can be option-
ally connected to the test socket of the trip unit, or - in case of longer stationary operation - to the last cmodule, and snapped onto
a 35-mm DIN rail. The required connection cables are supplied with the unit.
9.4.2

View

9.4.3

Indicators

LED
Indication
green
DEVICE
yellow
red
green
c
red
off
9.4.4

Connection versions

The BDA can, depending on the application, be connected in different ways.
NOTE
Connect the BDA to the trip unit prior to turning on the power supply.
Significance
BDA in operation
BDA in test mode
BDA faulty
c
connected available
c
Check connections and
c
No connection to
modules
9 – 93