Model - Gradient syncFURNACE mOD-200 Installation & Operation Manual

Table of Contents

Advertisement

18L MODEL:
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
0.1
FC HEAT OUTPUT [BTU/hr]
90 °F
900 CFM
15,481
1200 CFM
17,708
1500 CFM
23,837
1800 CFM
26,059
FC RETURN WATER TEMP [°F]
90 °F
900 CFM
83
1200 CFM
81
1500 CFM
80
1800 CFM
79
syncFURNACE OD Instruction & Installation Manual – Rev 09
900 CFM
1200 CFM
0.2
0.3
DUCT SYSTEM ESP
RPM SETTING TABLE
0.1
0.2
900 CFM
576
644
1200 CFM
697
756
1500 CFM
832
877
1800 CFM
978
1018
Heating Coil Supply Water Temp
110 °F
130 °F
140 °F
32,158
46,683
53,975
38,335
55,708
64,436
43,291
62,956
72,842
47,359
68,909
79,746
Heating Coil Supply Water Temp
110 °F
130 °F
140 °F
96
109
116
93
105
112
91
102
108
89
100
105
1500 CFM
0.4
Duct System ESP [inch w.c.]
0.3
0.4
709
775
813
861
923
960
1057
1095
FC SUPPLY AIR TEMP [°F]
90
150 °F
°F
61,280
900 CFM
82
73,184
1200 CFM
81
82,752
1500 CFM
80
90,612
1800 CFM
78
Assumptions
Coil Flow-rate = 4.5 GPM (5.49 ft head coil)
Pump spd 3
150 °F
Incoming Air Temp = 65 °F
123
118
113
110
1800 CFM
0.5
0.5
0.6
832
884
911
960
1014
1054
1132
1169
Heating Coil Supply Water Temp
110
130
140
150
°F
°F
°F
98
113
120
128
94
108
115
121
92
104
110
116
89
100
106
111
0.6
°F