5L MODEL:
3200
3000
2800
2600
2400
2200
2000
1800
1600
1400
1200
1000
0.1
FC HEAT OUTPUT [BTU/hr]
90 °F
300 CFM
6,657
400 CFM
8,115
500 CFM
9,324
600 CFM
10,342
FC RETURN WATER TEMP [°F]
90 °F
300 CFM
83
400 CFM
82
500 CFM
81
600 CFM
80
syncFURNACE OD Instruction & Installation Manual – Rev 09
300 CFM
400 CFM
0.2
0.3
DUCT SYSTEM ESP
RPM SETTING TABLE
0.1
0.2
300 CFM
1625
1738
400 CFM
2065
2155
500 CFM
2522
2595
600 CFM
2980
3046
Heating Coil Supply Water Temp
110 °F
130 °F
140 °F
12,050
17,481
20,206
14,713
21,369
24,713
16,926
24,606
28,466
18,790
27,336
31,634
Heating Coil Supply Water Temp
110 °F
130 °F
140 °F
98
113
120
95
109
115
93
106
112
91
103
109
500 CFM
0.4
Duct System ESP [inch w.c.]
0.3
0.4
1851
1966
2243
2330
2665
2736
FC SUPPLY AIR TEMP [°F]
90
150 °F
°F
22,936
300 CFM
85
28,063
400 CFM
84
32,336
500 CFM
82
35,943
600 CFM
81
Assumptions
Coil Flow-rate = 2 GPM (2.81 ft head coil) - pump spd1
150 °F
Incoming Air Temp = 65 °F
127
122
118
114
600 CFM
0.5
0.5
0.6
2075
2179
2418
2504
2809
2883
Heating Coil Supply Water Temp
110
130
140
150
°F
°F
°F
102
119
127
135
99
114
122
130
96
110
118
125
94
107
114
120
0.6
°F