Connecting A 6C205-2 To A 48/60 Vdc Power Source - Cabletron Systems 6C105 Overview And Setup Manual

Cabletron overview and setup guide smartswitch 6c105
Hide thumbs Also See for 6C105:
Table of Contents

Advertisement

Installation Requirement
Each DC power supply input requires either a 48 VDC or 60 VDC power
source supplied by three 10 AWG (American Wire Gauge) copper wires.
These wires must be terminated with either ring or spade terminals that
accept a #6 screw.
3.4.1
Connecting a 6C205-2 to a 48/60 VDC Power
Source
To connect the 6C205-2 to a 48/60 VDC power source, face the front of
the power supply, then refer to
DC Input Power Strip
Figure 3-7 48/60 VDC Power Supply Connections
To prevent injury or damage to the equipment, remove power
from a 48/60 VDC power source before proceeding with the
following steps.
1.
Connect the ground
appropriate earth ground.
2.
Refer to
Figure 3-7
source. Then connect the output leads of the 48/60 VDC power source
being used to the negative (-) and positive (+) terminals on the DC
input power strip.
3.
Repeat steps 1 and 2, if applicable, to connect a 48/60 VDC power
source to a second 6C205-2 installed in the chassis.
4.
Restore power to the 48/60 VDC power sources.
5.
Press the on/off power switch of each power switch to on.
6C105 Overview and Setup Guide
Powering Up a 6C105 with DC Power Supplies
Figure 3-7
ON/OFF
2016_98
terminal of the DC input power strip to an
for the proper connections to a 48/60 VDC power
and proceed as follows:
+
48 or 60 Vdc
-
Power Source
Earth
Ground