1. Connect the prefabricated cable to the ripple control receiver. The wiring is shown in the
following circuit diagram.
Insulated wire colour*
grey
white
brown
green
yellow
* DIN 47100 without colour repetition
2. Plug the 7-pole plug into the AUXCOM terminal on
the Power Reducer Box.
☑ The Power Reducer Box is connected to the ripple control receiver.
User Manual
Signal
+5 V
K1
K2
K3
K4
Power Reducer Box
AUXCOM terminal
6
1
2
4
5
REDUCERBOX-BA-en-16
7  Connection
Description
Voltage Supply
Relay contact 1
Relay contact 2
Relay contact 3
Relay contact 4