NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
Figure 4-13 Top view of compact installation if the quantity is ≤ 12 (NetCol500-
A060)
Figure 4-14 Top view of compact installation if the quantity is > 12 (NetCol500-
A060)
Figure 4-15 Top view of compact installation if the quantity is ≤ 6 (NetCol500-
A120)
Issue 05 (2020-10-10)
NO TE
Install the devices in a compact manner. If necessary, increase the height of the base. Take
the NetCol500-A060 as an example.
● When the quantity is 12 or less, if the wall height is 0 mm, the base height is 0 mm. If
the wall height is 1000 mm or lower, the base height is 500 mm or higher.
● When the quantity is more than 12, if the wall height is 0 mm, the base height is 500
mm or higher. If the wall height is 1000 mm or lower, the base height is 1000 mm or
higher.