Ensure that the rubber ring is not disconnected. If the rubber ring is disconnected
or damaged, seal the gaps around the pipes with mastic cement or thermal
insulation foam.
Step 3 Connect the hose to the adapter.
Step 4 Install the hose hoop.
Step 5 The drainpipe must be wrapped with the thermal insulation foam.
● The entire drainpipe should be closely wrapped with thermal insulation foam
(thickness of ≥ 3 mm is recommended).
● The drainpipe should be less than or equal to 3 m long with a certain gradient
(1:100 or larger is recommended). No upward or wavy bend is allowed, as
shown in the following figure.
Figure 4-77 Drainpipe installation specifications