Huawei NetCol8000-A045D User Manual page 294

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A045D:
Table of Contents

Advertisement

NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
● Do not frequently or quickly disconnect or connect the DP cable of the display
module. Do not forcibly pull the DP cable.
● You are advised to power off the main control board (or main control module)
and then replace the display module.
● If the main control board is not powered off, you are advised to back up the
configuration file of the product by referring to
1.
2.
3.
4.
5.
Issue 05 (2020-10-10)
CA UTION
Open the front door and do not damage the cables connected to the display
module.
Remove the cables from the display module.
Use a Phillips screwdriver to remove the four screws and gaskets that secure
the display module, and pull out the display module.
NO TICE
– When pushing the display module leftwards or rightwards, pay attention to
the buckles on the panel to prevent damage to the display module.
– The gasket is used to adjust the distance between the display module and
the door panel.
– The gasket dimensions are 25 mm (L) x 12 mm (W) x 2 mm (H) and the
center aperture is 6 mm.
Figure 11-27 Replacing a display module
Install the new display module in the original position on the front door by
performing the preceding steps in reverse order.
Connect the control signal cables to the display module. Close and lock the
front door.
Copyright © Huawei Technologies Co., Ltd.
11 Parts Replacement
step
1.
284

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents