NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
Tab
T/H Sensor
Issue 05 (2020-10-10)
Parameter
In-cabinet water
overflow alarm action
Temperature and
humidity control type
Temperature setpoint
Humidity setpoint
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Description
Set the action of the device if there is
water overflow in the cabinet based on
the actual scenario.
● Shutdown: The device shuts down
when an in-cabinet water overflow
alarm is generated.
● Inactivity: The device runs as usual
when an in-cabinet water overflow
alarm is generated.
● Only indoor fan running: Only the
indoor fan runs when an in-cabinet
water overflow alarm is generated.
● Humidifier stopped: Only the
humidifier is stopped when an in-
cabinet water overflow alarm is
generated.
When the application scenario is non-
aisle containment, you are advised to
choose Return air. Choose Cold aisle
if cold aisle T/H sensors are installed.
Hot aisle is not recommended.
After the temperature and humidity
control type and the temperature
value under this type are set, the
device performs cooling or heating
based on the settings.
● Return air temperature: 26–35°C
recommended
● Supply air temperature: 18–24°C
recommended
● Cold aisle temperature: 18–24°C
recommended
● Hot aisle temperature: 26–35°C
recommended
After the temperature and humidity
control type and the humidity value
under this type are set, the device
performs management based on the
settings.
40%–60% is recommended.
176