NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
Figure 4-4 Layout of bottom pipe routing (2)
(1) NetCol8000-A
Figure 4-5 Layout of side pipe routing
(1) NetCol8000-A
Issue 05 (2020-10-10)
NO TE
● The height of the raised floor for downflow units must be greater than 550 mm. (The
550 mm space under the floor is used only for fan rotation. The fan rotation area
cannot be occupied by pipes or cables.). Properly determine the positions for routing
pipes and cables to avoid interference.
● The height of the raised floor for upflow units is greater than 300 mm.
● L indicates the front maintenance distance for the device. The minimum maintenance
distance is 900 mm for the NetCol8000-A045, NetCol8000-A055, and NetCol8000-A090,
or 1100 mm for the NetCol8000-A060 and NetCol8000-A120. If the front distance
cannot meet the requirements, remove the front door for maintenance. The minimum
distance is 800 mm.
Copyright © Huawei Technologies Co., Ltd.
4 System Installation
55