Huawei NetCol8000-A045D User Manual page 108

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A045D:
Table of Contents

Advertisement

NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
Copper Pipe
Outer
Diameter
(inch)
5/8
3/4
7/8
1
1-1/8
To dampen noises generated by the equipment due to vibration, refrigerant pipe
supports should be installed as required by
Figure 4-55 Refrigerant pipe installation diagram
Issue 05 (2020-10-10)
45-degree
Bend (Unit:
m)
0.17
0.2
0.24
0.28
0.32
When the direction of the refrigerant pipe is changed, add a support at the
position that is 500 mm away from the changing point.
In a straight section of the refrigerant pipe, add a support every 1500 mm.
NO TE
Onsite personnel are responsible for preparing the required materials and installing the
supports.
Copyright © Huawei Technologies Co., Ltd.
90-degree
180-degree
Bend (Unit:
Bend (Unit:
m)
m)
0.3
0.6
0.35
0.7
0.42
0.8
0.5
1
0.6
1.2
Figure
4-55.
4 System Installation
T-shaped 3-
Way Valve
(Unit: m)
0.7
0.8
1.2
1.3
1.4
98