NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
Figure 4-3 Layout of bottom pipe routing (1)
(1) NetCol8000-A
Issue 05 (2020-10-10)
The smart cooling products should be placed as far away from offices as
possible, and noise control measures should be taken.
If the cap is configured, reserve space on the top of the indoor unit. The
height of the reserved space must be greater than that of the cap. For details,
see
4.11.5 (Optional) Installing a Cap (Applicable to Upflow
NO TE
● The height of the raised floor for downflow units must be greater than 550 mm. (The
550 mm space under the floor is used only for fan rotation. The fan rotation area
cannot be occupied by pipes or cables.) Properly determine the positions for routing
pipes and cables to avoid interference.
● The height of raised floors is greater than 300 mm for upflow units.
● W indicates the distance between smart cooling products. The minimum distance is 300
mm for upflow units or 500 mm for downflow units.
● L indicates the front maintenance distance for the device. The minimum distance is 900
mm for the NetCol8000-A045, NetCol8000-A055, and NetCol8000-A090, or 1100 mm
for the NetCol8000-A060 and NetCol8000-A120. If the front distance cannot meet the
requirements, remove the front door for maintenance. The minimum distance is 800
mm.
Copyright © Huawei Technologies Co., Ltd.
4 System Installation
Units).
54