Huawei NetCol8000-A045D User Manual page 165

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A045D:
Table of Contents

Advertisement

NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual
Table 6-1 Refrigerant charge amount
Indoor Unit
-
NetCol8000-
A045D
NetCol8000-
A045D
(including a
low
temperature
component)
NetCol8000-
A045U
NetCol8000-
A045U
(including a
low
temperature
component)
NetCol8000-
A090D
system 1
NetCol8000-
A090D
system 2
Issue 05 (2020-10-10)
Outdoor Unit
NetCol500-A060/
NetCol500-A120
system 1/
NetCol500-A120
system 2
NetCol500-A080
NetCol500-A060/
NetCol500-A120
system 1/
NetCol500-A120
system 2
NetCol500-A060/
NetCol500-A120
system 1/
NetCol500-A120
system 2
NetCol500-A080
NetCol500-W055
NetCol500-A060/
NetCol500-A120
system 1/
NetCol500-A120
system 2
NetCol500-A060/
NetCol500-A120
system 1
NetCol500-A080
NetCol500-A060/
NetCol500-A120
system 2
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Refrigerant Charge Amount (L) (L is total
one-way pipe length) (kg)
0 m < L ≤ 10
10 m < L ≤
m
60 m
9.4
9.4 + (L – 10)
x 0.21
13.4
13.4 + (L –
10) x 0.21
32.9
32.9 + (L –
10) x 0.21
8.8
8.8 + (L – 10)
x 0.21
12.8
12.8 + (L –
10) x 0.21
9.6
9.6 + (L – 10)
x 0.19
32.3
32.3 + (L –
10) x 0.21
9.4
9.4 + (L – 10)
x 0.21
13.4
13.4 + (L –
10) x 0.21
9.4
9.4 + (L – 10)
x 0.21
60 m < L ≤
100 m
9.4 + (L – 10)
x 0.28
13.4 + (L –
10) x 0.28
32.9 + (L –
10) x 0.28
8.8 + (L – 10)
x 0.28
12.8 + (L –
10) x 0.28
-
32.3 + (L –
10) x 0.28
9.4 + (L – 10)
x 0.28
13.4 + (L –
10) x 0.28
9.4 + (L – 10)
x 0.28