Daikin FTXA20A Service Manual page 83

Split stylish r32
Table of Contents

Advertisement

To check the wiring of the indoor unit power PCB
To check the fuse of the indoor unit main PCB
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
Is the correct spare part for the indoor
unit power PCB installed?
No
Prerequisite: First perform all earlier checks of the indoor unit main PCB, see
"2.9.1 Checking
procedures" [
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2 Check that no connectors or wires are damaged.
3 Check that the wiring corresponds with the wiring diagram, see
4
diagram" [
 171].
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Yes
No
Prerequisite: First perform all earlier checks of the indoor unit main PCB, see
"2.9.1 Checking
procedures" [
1 Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
a
a Fuse F1U
Blown fuse on the indoor unit power
PCB?
Yes
Action
Replace the indoor unit power PCB, see
"2.9.2 Repair
4
 81].
Action
No further actions required.
Return to
"2.8.1 Checking
procedures" [
power PCB and continue with the next
procedure.
4
 81].
Action
Replace the blown fuse, see
"2.9.2 Repair
2
Components
|
4
procedures" [
 84].
"5.2  Wiring
4
 75] of the indoor unit
4
procedures" [
 84].
Service manual
83