Daikin FTXA20A Service Manual page 55

Split stylish r32
Table of Contents

Advertisement

FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
a
c
a Nut
b Compressor
c Damper
INFORMATION
The compressor dampers may look different.
7 Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
8 Wrap a wet rag around the compressor pipes and any other components near
the compressor and solder the compressor pipes to the refrigerant pipes.
a
a Compressor pipe
CAUTION
Overheating the compressor pipes (and the oil inside the compressor pipes) will
damage or destroy the compressor.
9 After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
10 Connect the Faston connectors to the compressor wire terminals U, V and W
2
Components
|
b
a
c
a
c
a
Service manual
55