Daikin FTXA20A Service Manual page 56

Split stylish r32
Table of Contents

Advertisement

2
|
Components
Service manual
56
U Wire terminal U
V Wire terminal V
W Wire terminal W
11 Install the cover of the compressor wire terminals.
a Compressor wire terminals cover
12 Install the compressor insulation, see
13 Perform a pressure test, see
14 Add
refrigerant
4
procedures" [
 162].
Is the problem solved?
Yes
No
V
U
W
a
"2.2.2 Repair
"3.2.1 Checking
to
the
refrigerant
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
4
procedures" [
 52].
4
procedures" [
 158].
circuit,
see
"3.2.2  Repair
RXA20~35A(9) + RXA42+50B
ESIE18-03D – 2021.05
Split Stylish R32