FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
U Wire terminal U
V Wire terminal V
W Wire terminal W
CAUTION
Before measuring the compressor motor windings resistance, measure the
resistance of the multimeter probes by holding the probes against each other. If the
measured resistance is NOT 0 Ώ, this value MUST be substracted from the measured
winding resistance.
4 Measure the resistance between the compressor motor windings U-V, V-W
and U-W.
Result: All measurements MUST be approximately the same.
Compressor motor winding
measurements are correct?
Yes
No
5 Measure the continuity of the U, V and W wires between the compressor and
the PCB. If no continuity, correct as needed, see
6 Connect the Faston connectors to the compressor wire terminals U, V and W
V
U
W
Action
Continue with the next step.
Replace the compressor, see
"2.2.2 Repair
procedures" [
"5.2 Wiring
2
Components
|
4
 52].
4
diagram" [
 171].