2
|
Components
To install the humidity sensor
Service manual
72
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Disconnect the connector from the humidity sensor PCB.
2 Carefully click the complete humidity sensor PCB assembly out of the indoor
unit.
a Humidity sensor PCB assembly
3 To install the humidity sensor PCB assembly, see
4
procedures" [
 71].
1 Click the humidity sensor PCB assembly on the indoor unit.
a Humidity sensor PCB assembly
2 Connect the harness to the humicity sensor PCB assembly.
Is the problem solved?
Yes
No
"2.14 Plate
a
a
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
4
work" [
 120].
"2.6.2  Repair
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05