FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
2 Remove the cover of the compressor wire terminals.
a Compressor wire terminals cover
3 Disconnect the Faston connectors from the compressor wire terminals U, V
and W.
INFORMATION
Note the position of the Faston connectors on the compressor wire terminals to
allow correct connection during installation.
U Wire terminal U
V Wire terminal V
W Wire terminal W
4 Set the Megger voltage to 500 V DC or 1000 V DC.
5 Measure the insulation resistance between the following terminals. The
measured insulation resistance MUST be >3 MΩ.
▪ U–ground,
▪ V–ground,
▪ W–ground.
a
V
U
W
2
Components
|
Service manual
51