Web-based configuration
5.4 Web pages
4. Set the action type.
5. Configure the action.
– If the action is a variable change, you need to select a variable from the variable list
– If the action is sending a message, you need to select a message from the message list.
6. Enable the bind.
54
Action
1
Set new value
2
Copy value from
event
3
Increase by value
4
Decrease by value
5
Send message
6
Send variable
and fill the new value in the input box below To.
Action
Target restriction
source
variable
Permitted data type: all
UDM permitted data type.
The variable type of the
action must be the same as
the variable type of the
source event it copied from.
Permitted data type: all
UDM permitted data type
except bool.
Message
Variable
Remark
If the event is "receive mes-
sage" and the event source is a
message without variable,
then this action cannot be
configured.
•
The increase or decrease
value can only be positive.
•
If the variable reaches the
maximum or minimum
value of its range, the vari-
able will not increase or
decrease any more.
•
If the event is "receive
message", this action type
cannot be configured.
•
If the message contains a
parameter, the parameter
is the event parameter.
•
The format of the message
is:
variable name = value
(short type)
If the variable is in hexa-
decimal, 0x is added before
the value, for example,
v0.0 = 0x10(b)
•
If the event is "receive
message" and the event
source is a message with-
out variable, then this ac-
tion cannot be triggered.