FSDrive-MX1S Standard Specifications

Specifications by Model

The specifications of 3 kV class models and 6 kV class models are listed below.
All models from 3 kV class 200 kVA to 6 kV class 6000 kVA have the same electric specifications and control
specifications.
3 kV Class Models
Model CIMR-MX1S A
Max. Applicable Motor Capacity (kW)
Output Rating
Power Supply
Efficiency
Power Factor
Cooling Method
Control Specifi-
cations
Protective Functions
Communications Functions (optional)
Maintainability
Environmental
Specifications
General Specifi-
cations
* 1. Maximum applicable capacity of Yaskawa's 4-pole standard motors
* 2. Select the motor and set the motor constants so that the output voltage never exceeds 3300 V in any status, including transitions such as acceleration and deceler-
ation.
* 3. An uninterruptive input power supply unit (optional) for the control power supply is required to use the restart function for momentary power loss.
-2
9
Table 9.1 3 kV Class FSDrive-MX1S Standard Specifications
*1
Nominal Capacity (KVA)
Rated Output Current (A)
Rated Output Voltage (V)
Max. Output Frequency
Main Circuit (Input Voltage)
Control Circuit
Control Method
Main Circuit
Frequency Control Range
Frequency Control Accuracy
Analog Input Resolution
Acceleration/Deceleration Time
Main Control Functions
Control Panel
Main Circuit
Enclosure
Ambient Temperature and Humidity
Storage Temperature
Atmosphere
Paint Color
Applicable Standards
132
200
315
450
132
200
315
450
200
285
400
570
35
50
70
100
*2
Three-phase 3300 V
(sine wave)
120 Hz
Three-phase 3000/3300 V ±10%, 50/60 Hz ±5%
Three-phase 200/220 V, 50/60 Hz ±5%
Approx. 98% (at motor rated speed and 100% load)
0.95 min. (at motor rated speed and 100% load)
Forced air-cooling using an exhausting fan (with fault detector)
Open-loop vector control, flux vector control
Voltage type series multiplex
0.01 to 120 Hz
±0.5%
0.03 Hz
0.1 to 6,000 seconds
Restart after momentary power loss
during acceleration/deceleration, coasting to a stop, jump frequen-
cies, S-curve acceleration/deceleration, multi-step speed control,
etc.
Overcurrent, overvoltage, undervoltage, output ground fault, output
open-phase, overload, cooling fan fault, motor overheat, etc.
MODBUS, CP-215, CP-218 (Ethernet), etc.
Status display, fault display, setting/reading of commands and con-
stants
Module configuration
IP 40
–5 to +40°C, 85%RH max. (with no condensation)
–10 to +50°C
General environmental conditions (free from dust or corrosive gas),
altitude: 1,000 m max.
Internal and external surfaces painted in Munsell 5Y/7/1 semiglossy
JIS, JEC, JEM, Electric Facility Technical Reference
630
900
13C
18C
25C
630
900
1250
1800
2500
800
1150
1500
2300
3000
140
200
260
400
*3
, torque limit, stall prevention
520