Note: be sure there is no refrigerant inside the system and power supply has been cut off before
replacement.
Steps
1. Remove the front
panels.
2. Remove power
lines and the
electric heater.
3. Disconnect
power lines to the
compressor.
Test Operation, Troubleshooting and Maintenance
Replacement of the compressor
Image
• Remove screws at the front panel.
• Loosened screws should be put
together to avoid loss.
• Pull the front panel upwards and
then remove it.
• Properly keep the removed front
panel to avoid from being damaged.
• Loosen screws of power lines with a
screwdriver.
• Draw out power lines.
• Draw out the electric heater.
• Note that power lines and their
terminals should be numbered to
avoid incorrect rewiring.
• Desolder pipes quick to avoid
deformation.
• Keep the replaced compressor
complete for further analysis.