Note: properly reclaim refrigerant, prepare tools and keep good ventilation.
Steps
2. De-solder
connection pipes.
3. Take out the
vapor-liquid
separator.
4. Clean the
system by charging
nitrogen.
5. Replace it with a
new one.
Test Operation, Troubleshooting and Maintenance
Replacement of vapor-liquid separator
Image
De-solder connection pipes with a
soldering gun.
Loosen fixed screws and take out the
vapor-liquid separator.
• Connect a nitrogen line. When its
size is quite large, you need to
use adhesive tape for help to keep
nitrogen naturally go into the vapor-
liquid separator.
• Clean the system by charging
nitrogen.
Install the new vapor-liquid separator
as per reverse steps as stated above.