Gree LSQWRF35VM/NaA-M Service Manual page 90

A series modular air-cooled chiller (heat pump)
Hide thumbs Also See for LSQWRF35VM/NaA-M:
Table of Contents

Advertisement

(2) LSQWRF60VM/NaA-M, LSQWRF65VM/NaA-M and LSQWRF60VM/NhA-M
Note: be sure there is no refrigerant inside the system and power supply has been cut off before
replacement.
Steps
1. Remove the
front panels.
2. Remove power
lines and the
electric heater.
3. Disconnect
power lines to the
ompressor.
4. Loosen screws
at feet of the
compressor.
Test Operation, Troubleshooting and Maintenance
Replacement of the compressor
Image
• Remove screws at the front panel.
• Loosened screws should be put
together to avoid loss.
• Pull the front panel upwards and
then remove it.
• Properly keep the removed front
panel to avoid from being damaged.
• Note: there are two clasps at each
panel for connecting with side
panels.
• Remove the insulation of the
compressor.
• Loosen screws of power lines with a
screwdriver.
• Draw out power lines.
• Draw out the electric heater.
• Note: power lines and their
terminals should be numbered to
avoid incorrect rewiring.
• Desolder pipes quick to avoid
deformation.
• Keep the replaced compressor
complete for further analysis.
• Loosen screws at feet of the
compressor with a adjustable or box
spanner.
• Loosened screws should be put
together to avoid loss.
86