Page 1
Owner’ s Manual carefully before operation and retain it for future reference. If you have lost the Owner's Manual,please contact the local agent or visit www.gree.com or send an email to global@gree.com.cn for the electronic version. GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI...
Page 2
(6) The final right to interpret for this instruction manual belongs to Gree Electric Appliances Inc. of Zhuhai.
Page 3
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.Children should be supervised to ensure that they do not play with the appliance.
D Series Modular Air-cooled Scroll Chillers Safety Notices (Please be sure to abide ) WARNING: If not abide strictly, it may cause severe damage to the unit or the people. NOTE: If not abide strictly, it may cause slight or medium damage to the unit or the people.
Page 7
Do not do troubleshooting personally, as incorrect troubleshooting would lead to electrocution or fire • hazards. Instead, please contact GREE after-sales service center. When the unit is charged with refrigerant, do not solder or cut any pipeline, fined heat exchanger, shell- •...
Page 8
D Series Modular Air-cooled Scroll Chillers CAUTION D o not let the unit out of the designed application range; otherwise it would cause the heat exchanging • tube cracking, refrigerant leakage or even explosion. Do not let the cold/heat source directly act on the stored foods, plants, animals, precision instruments, •...
Page 9
D Series Modular Air-cooled Scroll Chillers Safety Precaution for Handling of the Unit ◆ (1) Precautions for Handling of the Unit WARNING Please contact the contractor for handling and installation. Improper installation would lead to • electrocution or fire hazard.
Excellent compatibility: ◆ Each D series modular air-cooled scroll chillers is constructed of up to 16 single units of 65D, 80D or up to 8 single units of 130D,160D which may vary in structure and in capacity. Free master module design: ◆...
D Series Modular Air-cooled Scroll Chillers Fig.1-1 Schematic Diagram 2 Product Data and Operating Range (1) See the Data Sheet for detailed product data. Data on the product nameplate always takes precedence. If there is any special requirement, consult the local sales office for model selection.
D Series Modular Air-cooled Scroll Chillers 3 Outline Dimension (1) Graph for the shape and dimensions for LSQWRF65M/D-M, LSQWRF80M/D-M (Unit:mm) (2) Graph for the shape and dimensions for LSQWRF65M/NaD-M, LSQWRF80M/NaD-M (Unit:mm) 967(Ground bolt) 1396 1750(Ground bolt 4-M12) 1000 2040...
Page 13
D Series Modular Air-cooled Scroll Chillers (3) Graph for the shape and dimensions for LSQWRF130M/D-M (Unit:mm) 1617(Ground bolt 4-M12) 1650 (4) Graph for the shape and dimensions for LSQWRF130M/NaD-M (Unit:mm) 1676 1617(Ground bolt 4-M12) 2026(Ground bolt 4-M12) 1650 2226...
Page 14
D Series Modular Air-cooled Scroll Chillers (5) Graph for the shape and dimensions for LSQWRF160M/D-M (Unit:mm) 1617(Ground bolt 4-M12) 1676 1650 2026(Ground bolt 4-M12) 2226 (6) Graph for the shape and dimensions for LSQWRF160M/NaD-M (Unit:mm) 1617(Ground bolt 4-M12) 1676 1650...
D Series Modular Air-cooled Scroll Chillers 4 Installation Instructions 4.1 General Installation should be performed by the skilled technician to guarantee the normal operation and prevent malfunctions and please read this manual carefully prior to installation. The chiller is manufactured, inspected and tested strictly in accordance with the quality control program and it will work properly within the expected service life as long as its installation, operation and service follow the instructions covered in this manual, otherwise, it would lead to potential risks.
D Series Modular Air-cooled Scroll Chillers 4.4 Installation Foundation (1) Installation foundation shall be designed by the qualified designer in accordance with the actual condition. (2) A rubber pad shall be placed under the base of each single unit and then secured on the ground or the roof.
D Series Modular Air-cooled Scroll Chillers 4.5 Vibration Reduction The unit shall be securely attached to the foundation through the mounting hole by following the steps below. (1) Be sure the planeness of the concrete foundation is within ±3mm and the foundation shall be covered by a rubber pad.
Page 18
D Series Modular Air-cooled Scroll Chillers (7) Under ultra-low temperature in winter, showdown at night will cause the evaporator and pipeline frozen up, so it is highly recommended to add alcohol and propanol mixture in chilled water. Do not cut off the power supply when the unit is turned off, otherwise the freeze protection does not work.
Page 19
D Series Modular Air-cooled Scroll Chillers Blind plug NOTE Keep the purge valve of the water system open in order to drain the evaporator and condenser • completely. Diameters of Entering/Leaving Water Pipes Diamter Cooling load (mm) (kW) DN15 DN20...
D Series Modular Air-cooled Scroll Chillers 5 Guidance to Controller Operation 5.1 Overview on Wired Controller In a 1~16 module network control system, only one Wired Controller is arranged for displaying the control menu, receiving and displaying parameters from the mainboard controller, setting adjustable parameters and transmitting set parameters to the mainboard controller.
D Series Modular Air-cooled Scroll Chillers 5.3 Wired Controller Operation Instructions 5.3.1 Turning on/off of the Unit The unit under non-commissioning state can be turned on/off via the manual mode or the timing mode. The manual mode is given priority to the timing mode.
Page 22
D Series Modular Air-cooled Scroll Chillers 5.3.2 Menu Operation Instructions Home page ◆ When the controller is powered on, the microcomputer will make a 3-second automatic detection and the LCD on the wired controller will display the following content. The content of default home page menu is dependent on system state. XX stands for year, month, day, hour and minute.
Page 23
D Series Modular Air-cooled Scroll Chillers Timer Setup ▲ Clock Setup Sound ON【OFF】 Backlight Page 2 Page 3 Press the Up or Down selection button to choose a needed function and press the Confirm to go to or confirm the selection. The subsequent “ON” or “OFF”, which means the function is selected or not.
Page 24
D Series Modular Air-cooled Scroll Chillers y Timer Setup Select Timer Setup and press Confirm to go to the page as shown in the following drawing: Press Confirm to change a selected object. Press Up or Down to change value or state of a selected object.
Page 25
D Series Modular Air-cooled Scroll Chillers (2) Module View When the Main Menu is present on the screen, select Module View, press the Confirm to go to the pages as shown in the following drawing. Module 1 XIST【NO】 Module 2 XIST【NO】...
Page 26
D Series Modular Air-cooled Scroll Chillers y Temperature View The function is for checking temperature at various temperature points. Select Temp. View and press the Confirm button to go to the pages as shown in the following drawings. C Water Tin XXX.X℃...
Page 27
D Series Modular Air-cooled Scroll Chillers y State View Used for checking the on/off status of motors. Select the State View and press the Confirm to go to the pages as shown in the following drawings. Sys.State 【Cool/Heat/Defrost/Anti-fre.】 ▼ Page 1...
Page 28
D Series Modular Air-cooled Scroll Chillers NOTE Above Items display is dependent on unit model. If this Item is not existent for a certain model, “NA” • would be present on the display zone for corresponding Item. y Error View Used for checking the failure status of the system.
Page 29
D Series Modular Air-cooled Scroll Chillers When the display is in Error View, select Clear History Error and press the Confirm button to go to the following interface. Clear History Error Press the Up or Down selection button to convert between NO and YES. Press YES to confirm and press NO to quit the menu and go back to the previous menu.
Page 30
D Series Modular Air-cooled Scroll Chillers (3) Parameter Setup On the Main Menu on the screen, select Parameter Setup and press Confirm to go to the page as shown in the following drawing. Press Exit to quit the page and go back to the previous menu. Press Up or Down selection button to select a needed setting interface.
D Series Modular Air-cooled Scroll Chillers (4) Version Information Used for checking version number of software and hardware of the wired controller. On the Main menu on the screen, select Version and press Confirm to go to the page as shown in the following drawing.
D Series Modular Air-cooled Scroll Chillers 5.5 Menu Structure...
Page 33
D Series Modular Air-cooled Scroll Chillers Menu Structure Explanation Menu Structure Explanation User’s Setup Function setting Run Mode Running modes selection Startup Startup and stop selection Auxiliary Heat Auxiliary heat function selection Auto-Antifreeze Auto anti-freezing function selection Timer setup Timer setting...
Page 34
D Series Modular Air-cooled Scroll Chillers Fan 3 Fan motor 3 status checking Sys.State Units system status checking Compressor1 Compressor 1 status checking Compressor2 Compressor 2 status checking C Water Pump Water pump status checking H Water Pump Hot water pump status checking Ass.
Page 35
D Series Modular Air-cooled Scroll Chillers Dis.T Sensor 2 Mal. Exhaust sensor 2 fail C Water-in Sensor Water in sensor malfunction C Water-out sensor Water out sensor malfunction Anti-Frozen Sensor Anti-freezing sensor malfunction Defrost T Sensor1 Defrosting sensor 1 malfunction...
D Series Modular Air-cooled Scroll Chillers 6 Electric Control Cabinet 6.1 Wiring for Output Control Lines Note: The output control lines of the auxiliary electric heater 1, auxiliary electric heater 2 and the water pump AC contactor are allowed to the terminal boards 11/12/13/14/15/16 of any module.
D Series Modular Air-cooled Scroll Chillers 6.3 Wiring of the Electric Control Cabinet 6.4 Filed Wiring Safety Code ◆ (1) All wiring shall comply with applicable codes and engineering requirements. (2) All field wiring shall be performed by the qualified electrician.
D Series Modular Air-cooled Scroll Chillers 6.6 Setup of Toggle Switches on the Motherboard Four bit toggle switches are used for indicating hardware address (1~16) of modules, with module No. displayed in turn on the panel as Module 1, Module 2, ……, Module 16. Toggle switches 1, 2, 3 and 4 are binary code, with 1 for the lowest bit and 4 for the highest bit.
D Series Modular Air-cooled Scroll Chillers 7 Commissioning and Maintenance The unit shall be maintained periodically by the skilled servicemen from Gree or a designed person under our professional guide to guarantee the unit operates reliably in a long term.
D Series Modular Air-cooled Scroll Chillers 7.3 Trial Run See the operation manual of the applicable controller for more details. (1) When the unit has not been used for a long period or the ambient temperature is quiet low, keep the...
(9) Check if the system vibration and noise are acceptable. 7.7 Parts Replacement Only parts supplied by Gree can be replaced instead of similar parts supplied by others. 7.8 Refrigerant Charging Refrigerant charging should be done based on the discharge and suction pressure. An air tight test must be taken on the condition refrigerant leaks or some part is required to be replaced.
D Series Modular Air-cooled Scroll Chillers (5) Remove the screw bolts of the compressor and check the oil quality and accumulator. (6) Remove the compressor. (7) Clean up the pipeline. 7.10 Freeze Protection When the flow passage of the shell-and-tube heat exchanger is frozen up, it would cause serious damage to the heat exchanger, such as cracking and leakage which are out of warranty, therefore, the user should take measures stated below for freeze protection.
D Series Modular Air-cooled Scroll Chillers 7.12 Precautions (1) Take periodic maintenance to the unit to guarantee normal operation. (2) Once refrigerant leaks, shut down the unit immediately and contact the serviceman. No open fire is allowed in that refrigerant will decompose into toxic gas.
Without commissioning, warranty will turned invalid under the following conditions: Refrigerant leaks in that the user personally opens some valve or pipe connector. • The user personally dismantles the unit without Gree’s approval. • The user personally powers the control cabinet or the compressor motor.
Page 46
D Series Modular Air-cooled Scroll Chillers Appendix A: Inspection Records Prior to Commissioning Installation Routine Check...
Page 47
D Series Modular Air-cooled Scroll Chillers Appendix B: Trial Run and Commissioning Records Trial Run Commissioning...
Page 48
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI Add: West Jinji Rd, Qianshan, Zhuhai,Guangdong, China, 519070 Tel: (+86-756) 8522218 Fax: (+86-756) 8669426 E-mail: gree@gree.com.cn www.gree.com...