4.1
4.2
Making the electrical connection
Table 5:
Designations for 1/1 x 19" casing with 2 TRM slots

Configuration for analog CT inputs

The secondary rated current of the CT (i.e. 1A or 5A) determines the choice of TRM in the IED.
Two TRMs are available, One is dimensioned for an input current of 5A and the other for an
input of 1A. If the CT rated secondary current does not match the TRM input current rating ad-
justments can be made in settings depending on the tolerance of the TRM.

Connecting to CT and VT circuits

CTs and VTs are connected to the TRM connection terminal on the rear-side of the IED.
Use a solid conductor with a cross section area between 2.5-6 mm
conductor with a cross section area between 2.5-4 mm
If the IED is equipped with a test-switch of type RTXP 24 COMBIFLEX wires with 20 A sock-
ets must be used to connect the CT and VT circuits.
Connectors X401 and X402 for current and voltage transformer circuits are so called
"feed-through IED blocks" and are designed for conductors with cross sectional area up to 4
2
mm
(AWG 12). The screws used to fasten the conductors should be tightened with a torque of
1Nm.
Module
Rear Positions
PSM
X11
BIM, BOM or
X31 and X32 etc. to X131 and
IOM
X132
MIM
X31, X41, etc. or X131
GSM
X131
SLM
X301:A, B, C, D
LDCM
X302:A, B
LDCM
X303:A, B
OEM
X311:A, B, C, D
LDCM
X312:A, B
LDCM
X313:A, B
TRM 1
X401
TRM 2
X411
2
(AWG14-12) or a stranded
2
.
Chapter 5
Installing the IED
31