Distance protection
11
X1+XN
10
40% of RLdFw
80% of RLdFw
alt. 80% of
RFPE (Load
encroachment)
Figure 27:
Distance protection (ZM) characteristic with test points for phase to earth mea-
surements
Table 16
is used in conjunction with
Table 15:
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Reach
Set value
X
X1
set
R
0
X
X1
set
R
R1
set
X
0.8 x X1
set
R
0.8 x R1
+ RFPP/2
set
X
0.5 x X1
set
R
0.5 x R1
+ RFPP/2
set
X
0.85 x RFPP x tan (ArgRLd)
R
0.85 x RFPP
X
RLdFw x tan (ArgLd)
R
RLdFw
X
RLdFw x tan (ArgLd)
R
0
X
–0.2143 x RFPP/2
R
0.8 x RFPP/2
X
2
1
80%
3
50%
4
12
5
6
7
13
9
8
RFPE
en05000369.vsd
figure
27.
Comments
ArgRLd = angle for the maximal load transfer
Exact: 0.8 x RFPP/2 (ArgDir)
Verifying settings by secondary
(Ω / loop)
R
Chapter 11