ABB REL670 Installation And Commissioning Manual page 71

Line distance protection ied
Hide thumbs Also See for REL670:
Table of Contents

Advertisement

About this chapter
Table 12:
Setting parameters for the session timers
Parameter
Range
SessionTmo
1-60
RetryTmo
100-10000
IdleAckCycle
1-30
BusyAckTmo
100-5000
ErrNackCycle
100-10000
Path in local HMI: Settings\General settings\Communication\SLM configuration\Rear optical
LON port
Table 13:
LON commands
Command
Command description
ServicePinMsg
Command with confirmation. Transfers the node adress to the LON network tool.
LONDefault
Command with confirmation. Resets the LON communication in the terminal.
verifying the LON communication
Default
Unit
Parameter description
20
s
Session timeout. Only to be changed
after recommendation from ABB.
2000
ms
Retransmission timeout.Only to be
changed after recommendation from
ABB.
5
s
Keep active ack.Only to be changed after
recommendation from ABB.
300
ms
Wait before sending ack.Only to be
changed after recommendation from
ABB.
500
ms
Cyclic sending of nack. Only to be
changed after recommendation from
ABB.
Chapter 9