ABB REL670 Installation And Commissioning Manual page 102

Line distance protection ied
Hide thumbs Also See for REL670:
Table of Contents

Advertisement

Test point
Value
8
X=0.2· RLdFw ·tan( ArgDir )
R=0.2· RLdFw
9
X=0.2· X1
0.2
=
R
tan(
ArgNegDir
10
X=0.85· X1set
0.8
=
R
tan(
ArgNegDir
11
X=0.2· X1
0.2
X
1
=
R
°
tan(60 )
12
X=0
R=0.5·RFFwPP
94
Distance protection
X
1
90)
X
1
90)
The table showing test points for phase to phase loops is used together with
Verifying settings by secondary
Comments
≈ −
X
0.054 RLdFw
R
0.432
X
1
R
1,727
X
1
R
0.346
X set
1
Note! This test points is proposed to be used instead of
point 4, 5 and 6 when shaped load characteristic is not
activated (OperationLdCmd=OFF)
Chapter 11
injection
figure
29.