6.7.5
110
Current protection
Checking the case without re-trip, RetripMode = Off
Procedure
1.
Set RetripMode = Off .
2.
Apply the fault condition, including start of BFP, well above the set
current value.
3.
Verify that no re-trip, but back-up trip is achieved after set time.
4.
Disconnect AC and start input signals.
Checking the re-trip with current check, RetripMode = I> check
Procedure
1.
Set RetripMode = I> check.
2.
Apply the fault condition, including start BFP, well above the set cur-
rent value.
3.
Verify that retrip is achieved after set time t1 and back-up trip after
time t2
4.
Apply the fault condition, including start of BFP, with current below
set current value.
5.
Verify that no re-trip, and no back-up trip is obtained.
6.
Disconnect AC and start input signals.
Checking re-trip without current check, RetripMode= No I> check
Procedure
1.
Set RetripMode = No I> check.
2.
Apply the fault condition, including start of BFP, well above the set
current value.
3.
Verify that re-trip is achieved after set time t1 , and back-up trip after
time t2 .
4.
Apply the fault condition, including start of BFP, with current below
set current value.
5.
Verify that re-trip is achieved after set time t1 , but no back-up trip is
obtained.
6.
Disconnect AC and start input signals.
Verifying the back-up trip mode
In the cases below it is assumed that FunctionMode = Current is selected.
Checking that back-up tripping is not achieved at normal CB tripping
Use the actual tripping modes. The case below applies to re-trip with current check.
Chapter 11
Verifying settings by secondary
injection