Overview Of Configuration Options - Siemens SIMATIC ET 200AL System Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

3.1.3

Overview of configuration options

Introduction
The tables below show the configuration options offered by the SIMATIC IO-Link master with
or without S7-PCT and which FW versions of the IO-Link master support the individual
configurations.
Comparison of the configuration options
The following table provides an overview of the available options for configuration with and
without S7-PCT:
Requirement
Use of the IO-Link device
description IODD
Setting the length of input
and output data (per port)
Assignment of the Vendor ID
and Device ID
Behavior during IO-Link
device replacement
Adjustable IO-Link cycle time
Adjustable IO-Link device
parameters
Display of the IO-Link pro-
cess data structure
Monitoring of IO-Link pro-
cess data
Display of IO-Link device
diagnostics messages
IO-Link system
Function Manual, 12/2017, A5E31637677-AB
Configuration with S7-PCT
Yes
Automatic
Automatic
Programmable
Yes
Yes
Yes
Yes
Yes
Integration into the automation system
3.1 Configuration of the IO-Link system
Configuration without S7-PCT
IO-Link Autostart
No
Manual
-
(https://support.industry.siem
ens.com/cs/ww/en/view/1097
-
No
No
No
No
No
IO-Link Manual
No
Manual
Manual (see FAQ
48852))
Programmable
No
No
No
No
No
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents