Siemens SIMATIC ET 200AL System Manual page 2215

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Error code
Meaning
(DW#16#...)
10100000
The send clock is outside the permitted range of 0 <
SEND_CLOCK <= 4 ms and is therefore invalid.
The error code can also indicate that
The data in TIO_SYNC_Data is invalid or does not
exist.
The TIO_DQ instruction is not called in an isochronous
OB.
00110000
The assigned value at the Out_Mode input parameter is
outside the valid range of 0 to 3.
x0130000
MC-Servo (OB91) is not isochronous to the bus cycle
time.
10140000
The configured value at the HWID input parameter is not
present in the structure at the TIO_SYNC_Data
parameter. The HWID and TIO_SYNC_Data parameters
are not consistent.
x0FF0000
General internal error.
High-precision input/output with Time-based IO
Function Manual, 11/2019, A5E33454822-AC
Solution
Correct the send clock.
Correct the value at the Out_Mode input
parameter.
Correct the value of the cycle time of the MC-
Servo to the value of the bus cycle time.
Note:
Calling TIO instructions in an OB of the type
"MC-PostServo" with reduction ratio "MC-
Servo" can result in incorrect calculation of time
stamps.
Correct the value at the HWID input parameter
or the structure at the TIO_SYNC_Data
parameter.
Programming
4.3 Time-based IO
57

Hide quick links:

Advertisement