Siemens SIMATIC ET 200AL System Manual page 2207

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Error code
Meaning
(DW#16#...)
10060000
No TIO module found.
Possible cause:
The module configured using the hardware identifier is
not a TIO module.
10070000
An internal error occurred during the address calculation. Check the value at the HWID input parameter.
00080000
TIO module is not synchronized using the TIO_SYNC
instruction.
The error code can also indicate that:
A job was already present before the first run of the
instruction.
The assigned number at the Channel input parameter
is not a digital input.
10090000
The read cycle time of the isochronous OB is outside the
permitted range of 0 < T
invalid.
The instruction can only be used without errors in an
isochronous OB.
100A0000
The time T
is outside the permissible range of 0 < T
100Bxxxx
An error has occurred during execution of the RD_ADDR
system function. The low word xxxx displays the error
information of the RET_VAL return value from
RD_ADDR.
000C0000
The converted time stamp is invalid.
Possible cause:
Communication error
000D0000
The Quality Information of the digital input indicates that
an error has occurred at the digital input.
000E0000
The assigned number at the Channel input parameter is
not a digital input configured as Timer DI.
000F0000
The assigned value at the EdgeSel input parameter is
outside the valid range of 1 to 5.
High-precision input/output with Time-based IO
Function Manual, 11/2019, A5E33454822-AC
<= 16 ms and is therefore
APP
of the TIO model stored in TIO_SYNC_Data
O
Solution
Make sure that the configured module is a
TIO module.
Check the value at the HWID input
parameter. Specify the hardware identifier of
the TIO module from its module properties in
the hardware configuration.
Specify the hardware identifier of the TIO module
from its module properties in the hardware
configuration. An internal system constant of
data type Hw_SubModule is available for the
symbolic addressing.
Check the instruction TIO_SYNC.
Correct the cycle time.
Make sure that TIO_DI_ONCE is called in a
"Synchronous Cycle" or "MC-PostServo" OB.
Check the instruction TIO_SYNC.
<= 4 ms.
o
Read the description of the RD_ADDR in the
STEP 7 (TIA Portal) information system.
Check the communication with the TIO module.
Check the supply voltage L+/1L+/2L+.
Check the channel configuration (only for
TM Timer DIDQ 16x24V).
Check the operating mode of the digital input.
Correct the value at the EdgeSel input
parameter.
Programming
4.3 Time-based IO
49