2
ANALOG INPUT MODULE REPLACEMENT
Item
Maximum conversion speed
Response time
Absolute maximum input
Analog input points
Maximum number of writes for
2
E
PROM
Isolation method
Dielectric withstand voltage
Insulation resistance
Occupied I/O points
Connected terminal
Applicable wire size
Applicable solderless terminal
Internal current consumption
(5VDC)
Weight
2
- 53
Between the input terminal and programmable controller power supply: photocoupler isolation
Between channels: non-isolated
Between the I/O terminal and programmable controller power supply: 500VAC, for 1 minute
Between the I/O terminal and programmable controller power supply: 500VDC, 5M or more
(I/O assignment: special 32 points)
(Applicable tightening torque: 39 to 59N•cm)
V1.25-3, V1.25-YS3A, V2-S3, V2-YS3A
A68ADN
20ms/channel
-
Voltage: ±15V
Current: ±30mA
8 channels/module
-
32 points
38-point terminal block
2
0.75 to 2mm
0.4A
0.51kg