3
ANALOG OUTPUT MODULE REPLACEMENT
16-bit signed binary
(Normal resolution mode: -4096 to 4095,
High resolution mode: -12288 to 12287, -16384 to 16383)
Voltage: -10 to 10VDC (External load resistance value: 1k to 1M)
Current: 0 to 20mADC (External load resistance value: 0 to 600)
Normal resolution
Analog output range
Digital input
0 to 5V
1 to 5V
Voltage
-10 to 10V
-4000 to
User range
settings
0 to 20mA
4 to 20mA
Current
User range
-4000 to
settings
Ambient temperature 25±5°C: within ±0.1%
(voltage: ±10mV, current: ±20µA)
Ambient temperature 0 to 55°C: within ±0.3%
(voltage: ±30mV, current: ±60µA)
Max. 100,000 times
Q64DAN
High resolution
mode
mode
Digital input
Maximum
value
value
resolution
1.25mV
0 to
0 to
4000
12000
1.0mV
-16000 to
2.5mV
16000
4000
-12000 to
0.75mV
12000
5
A
0 to
0 to
12000
4000
4 A
-12000 to
1.5 A
4000
12000
80µs/channel
Voltage: ±12V
Current: 21mA
4 channels/module
Available
: Compatible,
Compatibility
Maximum
resolution
0.416mV
0.333mV
0.625mV
0.333mV
1.66 A
1.33 A
0.83 A
: Partial change required, ×: Incompatible
Precautions for replacement
3