Buffer Memory Address Comparison - Mitsubishi Electric MELSEC-A/QnA Series Handbook

Table of Contents

Advertisement

3
ANALOG OUTPUT MODULE REPLACEMENT

3.4.4 Buffer memory address comparison

Sequence program change is required as the assignment of buffer memory differs.
For details of the buffer memories and sequence program, refer to the Digital-Analog Converter Module
User's Manual.
A62DA
Address
Name
(decimal)
0
CH1 Digital value
1
CH2 Digital value
2
CH1 Voltage setting value check code
3
CH2 Voltage setting value check code
4
CH1 Current setting value check code
5
CH2 Current setting value check code
3
- 25
Address
Read/write
(decimal)
0
D/A conversion enable/disable
1
CH1 Digital value
2
CH2 Digital value
R/W
3
4
5
System area (Not used)
to
10
11
CH1 Setting value check code
12
CH2 Setting value check code
13
to
System area (Not used)
18
19
Error code
20
Setting range (CH1 to CH2)
21
System area (Not used)
Offset/gain setting mode
22
Offset specification
Offset/gain setting mode
23
Gain specification
24
Offset/gain adjusted value specification
25
to
System area (Not used)
157
158
Mode switching setting
159
160
to
System area (Not used)
199
200
Pass data classification setting
201
System area (Not used)
202
CH1 Industrial shipment settings offset value
203
CH1 Industrial shipment settings gain value
204
CH2 Industrial shipment settings offset value
205
CH2 Industrial shipment settings gain value
206
CH1 User range settings offset value
207
CH1 User range settings gain value
208
CH2 User range settings offset value
209
CH2 User range settings gain value
Q62DAN
Name
Read/write
R/W
R/W
R/W
R/W
R/W
-
R
-